Permit: T04CM03815

Parcel: 11449030A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/21/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/16/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) VDV CABELING TO BE SUPPORTED UP OFF OF GRID
2) FINISH BOX MAKE-UP
3) OK LIGHTING AND ELECTRIC ROOMS 127-132, 136, 140 AND 101
08/11/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK 3 BOXES IN STAGE STEPS-BOXES IN COMBUSTIBLES TO BE FLUSH AND GROUND BOXES
2) OK ABOVE CEILING ROOM 115-117, 120, 122-124
3) CORRECTLY PHASE CONDUCTORS IN BOXES 210.5(C) AMENDMENTS
08/10/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) MANUFACTURES CLIPS FOR LIGHTS TO BE EFFECTIVE
2) FINISH BOX MAKE-UP
3) SUPPORT WIRES FOR RECESSED CANS