Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM03803
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
09/29/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PLUMBER TAPE NOT ALLOWED TO SUPPORT WASTE LINE 2) PVC TRANSITION TO COPPER PVC SHALL BE MALE ADAPTOR 3) SHIM EXISTING GIRDERS WHERE NOTCHED |
|
09/28/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LEAK ON 1/2" 90 DEGREE ABOVE BEDROOM #2 2) PROVIDE WATER TEST ON DWV SYSTEM |
|
09/24/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
09/20/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) SANITARY 'T' FITTINGS CANNOT BE USED IN THE FLAT HORIZONTAL DRAIN MUST USE DIRECTIONAL FITTINGS 2) SHOWER MUST BE 2" DRAIN AND TRAP 3) SHOWER NOT VENTED 4) VENT 90 FITTINGS CANNOT BE USED AT THE BOTTOM OF A VERTICAL DRAIN 5) HOUSE IS NOT PLUMBED PER PLAN OR CODE 6) NO WATER TEST ON DWV 7) STOPPED INSPECTION |
|
09/17/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CANNOT REDUCE DRAIN PIPE SIZE. WASHERS 2" TO 1 1/2"; BATH OUTSIDE. LINE 4" TO 3" TO 4" |