Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/29/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/OK ROUGH 1)COMPLETE #6, 11, 9-12 OF PREVIOUS INSPECTION | |
| 10/28/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/PANEL RELATED WORK TO BE COMPLETED 10/28/04 - RECALL FOR 10/29/04 1)SUPPORT CABLE WITHIN 12" OF BOXES & PANEL 2)PROTECT CABLES AT STUDS 3)USE APPROVED CONNECTOR WITH BOXES 4)SUPPORT WITH CORRECT MEANS - THHN IS NOT APPROVED 5)INSULATION ON SPLICES TO BE EQUAL TO ORIGINAL 110-14 6)SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 7)CLEAN SURFACE BENEATH LUG 8)BONDING JUMPER TO BE SIZED AS PER 250-122 9)FILL UNUSED OPENINGS IN BOXES 10)GROUNDING EQUIPMENT CONDUCTORS TO BE INSTALLED AS PER MANUFACTURES INSTRUCTION 11)ONLY (1) ONE NEUTRAL PER LOG 12)SEPERATE GROUNDS FROM NEUTRAL AT SUB PANEL 13)ELECTRICAL COVER TO BE NON COMBUSTABLES AT PANEL & JUNCTION BOX |