Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL 4 UNITS A-D |
|
| 12/30/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH 3 6 OF INSPECTION DATED 12/22/04 ALSO 1/4" AT NON COMBUSTIBLES. 2) A FITTING IS NEEDED AT ??TO SECURE CABLES TO ENCLOUSER | |
| 12/28/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) REVISED PLANS NEED CITY APPROVED STRAP 2) WE STILL HAVE PAINT ON LIVE PARTS |
|
| 12/23/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY ELECTRICIAN |
|
| 12/22/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WHERE IS LIGHTING PLAN-NO LIGHTS OR FANS ON WHAT YOU HAVE ON SITE 2) MAINTAIN WORKING CLEARANCE IN FRONT OF PANEL 3) CLEAN SURFACE IN PANEL OF EXCESSIVE PAINT 4) SWITCHES TO BE GROUNDED 5) MISSING ISLAND RECEPTACLES 6) APPROVED EXTENDER RINGS NEEDED AT COMBUSTIBLES 7) WEATHER PROOF COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGED INTO 406.8 8) CLOSE JUNCTION BOXES IN CARPORT 9) LABELS AT MAIN TO BE LEDGIABLE 10) TIGHTEN LOOSE SEAL TITE FITTING |