Permit: T04CM03787

Parcel: 141175030

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03787

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2004 FRAMING Approved IVRS - Inspection :*
10/05/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) PINS 12" ON CENTER 2) OVERSPAN 3) SHEAR TRANSFER 4) OK TO NET
10/04/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) INSTALL 5/8" DIAMETER A.B. FOR LTT20. H.D.'S (3 TOTAL) 2) NAIL OFF SHEAR AT GARAGE WALL, VERTS AT 16" ON CENTER 3) SW5 SHEARWALL PINS AT 12" ON CENTER, AND BLOCKED 4) NEED SWITCH LEG TO REAR PORCH LITE 5) ADD, OUTLET IN LIVING ROOM 6) SEE BLACK MARKS ON FLOOR 7) FIRE BLOCK LIVING POP OUTS FRONT WALL