Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/REVISIONS MADE ON PLANS GATE 9/13/04. CORRECTIONS COMPLETES PER R HOLLANDER WRITE UP 9/7/04. |
| 10/12/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* COULD NOT UNDERSTAND MESSAGE UNIT LOCKED |
| 09/07/2004 |
ELECTRIC - FINAL |
|
Partial Approval |