Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM03732
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
08/09/2005 | FRAMING | Partial Approval | IVRS - Inspection :* | |
08/08/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNABLE TO ENTER TO INSPECT 2) FRONT GATE LOCKED |
|
06/24/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) STUCCO LATH NOT COMPLETE-MUST BE COMPLETE BEFORE INTERMEDIATE INSPECTION CAN BE APPROVED 2) MANY BEARING STUDS NOTCHED MORE THAN 25 PERCENT-REPLACE 3) DBL TOP PLATES NOTCHED AT GLUE-LAM BEAMS. PROVIDE FHA STRAPS 4) JIM CAP-TEST CAP CANNOT BE ENCLOSED IN WALL CAVITY-MUST BE PERMANENT CAP AT KITCHEN 5) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 6) A/C REQUIRES 3/4" CONDENSATE 7) CONDENSATE OVERFLOW CANNOT BE ENCLOSED IN CEILING-PROVIDE INSTALLATION MANUAL FOR A/C 8) FIRESTOP SECOND FLOOR INCLOSED AREAS FLOOR AND CEILING 9) CUT OFF TJI BY STAIR REQUIRES SUPPORT 10) STAIR RISERS HAVE MORE THAN 3/8" DIFFERENCE IN RISE 11) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 12) STOPPED INSPECTION-TO MANY ITEMS |
|
03/01/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE AND RECALL CLIP AND SHEATHING/ROOF NAILING INSPECTIONS |