Permit: T04CM03730

Parcel: 126120210


Addresses:

4618 E 5TH ST

Inspection Status: Denied

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/07/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOT WATER HEATER PRESSURE RELIEF LINE MUST BE HARD PIPED NO FLEX
2) MISSING HIGH VENT WATER HEATER ROOM 100 CUBIC INCHES
3) PROVIDE SAFE ACCESS TO ROOF TOP UNIT
4) VACUUM BREAKER HOSE BIBS
5) IF ROOF TOP UNIT HAS INTAKE WATER HEATER B-VENT NEEDS ? CLEARANCE
6) YARD WATER COVERED WITHOUT INSPECTION
7) PROVIDE PROOF OF 1030 & 1025 APPROVALS