Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :OK TO CLEAR OK C OF O | |
| 12/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CALLED PHONE NUMBER PER REQUEST-GAVE 1/2 HR NOTICE-NO SHOW 2) RECALL-UNIT MUST BE OPEN 3) NEED PLANS AND PERMIT CARD |
|
| 12/08/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED PLANS/PERMIT 2) UNIT LOCKED |
|
| 12/03/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) ARC FAULT BREAKERS NOT INSTALLED YET |
|
| 12/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*NOTE: CUSTOMER CALLED 8:15 AM TO CANCEL INSP; R MAJUTA NOTIFIED. |
|
| 12/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MUST HAVE OUTLET SPACING NOT TO EXCEED 12' ON WALLS PER NEC. OUTLETS ABOVE BASE HTRS TO BE RE-LOCATED NEXT TO BASE BOARD HTR BUT NOT ABOVE 2) PERMITS ISSUED AS OF JULY 1-04 FALL UNDER 2004 NEC REQUIREMENTS, BEDROOMS CIRCUITS MUST BE ON ARC-FAULT CIRCUIT BREAKERS |
|
| 11/26/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PANEL NOT MADE UP. COVER TO PANEL DOES NOT OPEN TO 90 DEGREES FREELY. BASE BOARD HEATERS NOT INSTALLED. | |
| 11/24/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/23/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL BRACE FOR A/C DISCONNECTS 2) COMPLETE INSTALL OF BASE BOARD HTRS 3) THESE COMPLIANCES ARE FOR BOTH UNITS |
|
| 11/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)INSTALL EVAP'S 2)FINISH CIRCUIT TIE INTO BREAKERS 3)HOW IS SERVICE GROUNDED & WATER BONDED? SWITCHES IN BEDROOMS - ONE FOR FAN, ONE FOR LIGHT, NOT 2 SWITCHES FOR BOTH 4)OCCUPANT MUST HAVE ACCESS TO SERVICE AND OVER CURRENT DEVICES - FENCE PREVENTS THIS |