Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/REVISED PLAN NOT AT SITE. PLEASE CALL WHEN PLANS ARE APPROVED. OK TEMP C/O |
|
| 10/15/2004 | ELECTRIC - FINAL | Not ready for Inspection | ||
| 10/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : NEED TO LABEL SWITCHBOARD DISCONNECT. HAVE FUSER ON HAND. IMPROPER SUPPORT OF 2" EMT CONDUIT. NEED W/IN 3FT OF PANEL AND 10' THEREAFTER, NEED TO HAVE ?? TO STORE CEILING TO VERIFY PROPER SUPPORT. NEED APPROVED ?? FOR A/C UNIT. CANNOT HAVE CORD ABOVE CEILING. NEED TO HAVE ONE SCREW EACH SIDE OF 2X4 CEILING FIXTURE. LABEL ALL DISCONNECT AND CIRCUIT. |