Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T04CM03701
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2004 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* OK TO CLEAR ECO. CALL FOR FINAL AFTER TIE IN | |
09/15/2004 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| GROUNDING WIRE MUST BE CONNECTED TO GEOUND BAR IN PANEL, BOTH GROUND RODS TO BE CONNECTED TOGETHER WITH GROUND WIRE A RE-FEE WILL BE ASSESED NEXT INSP IF NOT FIXED |
|
09/10/2004 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :*/INSTALL 2 GROUND RODS 6' MIN APART-BOND GAS & WATER PIPES NOTE: BE SURE TO USE BOND BUSHINGS ON 1" CONNECTORS IN PANEL BECAUSE CONCENTRIL? KO'S WILL CK ON FINAL |
|
08/31/2004 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :*/ 1) PERMIT REQUIRED, APPROVED PLAN FOR ADDITION, NO CLEARANCE FOR SERVICE TILL ADDITION PERMITTED | |
08/30/2004 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| NO COMPLIANCE WITH LAST INSP WRITE UP - | |
08/25/2004 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITTED TO COVER 2) SUPPORT CONDUITS PER CODE, TIGHTEN FITTINGS, CONDUIT ON ROOF NOT SEATED INTO COUPLING PROPERLY, SUPPORT SO AS NO TO BEND AT COUPLINGS 3) USE BOND BUSHINGS ON 1" CONDUIT TERMINATIONS AT CONCENTRIC KO'S |