Permit: T04CM03701

Parcel: 129064790


Addresses:

2714 E 21ST ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Permit Number - T04CM03701

Inspection Description - ELECTRIC - SERVICE RELOCATION

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2004 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :* OK TO CLEAR ECO. CALL FOR FINAL AFTER TIE IN
09/15/2004 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| GROUNDING WIRE MUST BE CONNECTED TO GEOUND BAR IN PANEL, BOTH GROUND RODS TO BE CONNECTED TOGETHER WITH GROUND WIRE
A RE-FEE WILL BE ASSESED NEXT INSP IF NOT FIXED
09/10/2004 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*/INSTALL 2 GROUND RODS 6' MIN APART-BOND GAS & WATER PIPES
NOTE: BE SURE TO USE BOND BUSHINGS ON 1" CONNECTORS IN PANEL BECAUSE CONCENTRIL? KO'S WILL CK ON FINAL
08/31/2004 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*/ 1) PERMIT REQUIRED, APPROVED PLAN FOR ADDITION, NO CLEARANCE FOR SERVICE TILL ADDITION PERMITTED
08/30/2004 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| NO COMPLIANCE WITH LAST INSP WRITE UP -
08/25/2004 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITTED TO COVER 2) SUPPORT CONDUITS PER CODE, TIGHTEN FITTINGS, CONDUIT ON ROOF NOT SEATED INTO COUPLING PROPERLY, SUPPORT SO AS NO TO BEND AT COUPLINGS 3) USE BOND BUSHINGS ON 1" CONDUIT TERMINATIONS AT CONCENTRIC KO'S