Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/23/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) THE RECEPTACLES SUPPLIED TO POWER THE EXAM CHAIR MUST BE IDENTIFIED PER NEC 517.11 AND 517.16. THEY MUST BE INSULATED GROUNDING TERMINAL TYPE WITH GREEN DOT ON FACE |