Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM03699
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/18/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FINISH PREVIOUS INSPECTION ITEM 1, 2, 3, 2) FILL UNUSED OPENINGS IN BOXES 3) BOXES MORE THAN 1/4" FROM BOX TO SUFACE NEED APPROVED EXTENDER RING 4) PLEASE PROVIDE A LETTER DELETING OUTLETS. | |
01/11/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*1) SUPPORT FIXTURES AT 4 CORNERS OR 2 ON CENTER TO GRID 2) SUPPORT M/C CABLE AS PER 300.11 & 334 3) VDV CABLEING TO BE AS PER 725.2 725.6, 800.6 4) CHECK CONDUCTOR FILL AT BOXES |