Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM03699

Parcel: 110113620

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM03699

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/18/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* 1) FINISH PREVIOUS INSPECTION ITEM 1, 2, 3, 2) FILL UNUSED OPENINGS IN BOXES 3) BOXES MORE THAN 1/4" FROM BOX TO SUFACE NEED APPROVED EXTENDER RING 4) PLEASE PROVIDE A LETTER DELETING OUTLETS.
01/11/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*1) SUPPORT FIXTURES AT 4 CORNERS OR 2 ON CENTER TO GRID 2) SUPPORT M/C CABLE AS PER 300.11 & 334 3) VDV CABLEING TO BE AS PER 725.2 725.6, 800.6 4) CHECK CONDUCTOR FILL AT BOXES