Permit: T04CM03699

Parcel: 110113620

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/19/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/18/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* 1) FINISH PREVIOUS INSPECTION ITEM 1, 2, 3, 2) FILL UNUSED OPENINGS IN BOXES 3) BOXES MORE THAN 1/4" FROM BOX TO SUFACE NEED APPROVED EXTENDER RING 4) PLEASE PROVIDE A LETTER DELETING OUTLETS.