Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) ITEM #4036 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR C. WILLIAMS |
|
| 08/22/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSULATE ALL SUPPLY/RETURN AIR DUCTS 2ND FLOOR 2) INSULATION ON ROOF TOP DUCTWORK = R-8 2000 IEC. 3) NEED PERM. LADDER, SERVICE ACCESS ON ROOFS 16'0" OR HIGHER |