Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL RANGE TAILS PROPERLY, AND INSTALL ANTI-TIP BRACKETS ON RANGES 2) INSTALL LIGHTS AT WATER HEATERS 3) NEED SERVICE OUTLET FOR RTU'S ON ROOF NEC 210.63 |
|
| 02/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT 1 1. WIRE GROUND FOR WATER HEATER 2. MAX 15 AMP BREAKER FOR 14 GA WIRE INSTALL PROPER SIZE BREAKER BLANK 3. NEED LIGHT OR SWITCHED OUTLET IN HABITABLE ROOMS. 4. SMOKE DETECTORS NEED TO BE INTER-CONNECTED 5. INSTALL RANGE 6. NEED SERVICE OUTLET FOR EQUIPMENT ON ROOF AND MAX 30 AMP FUSES 7. CHECK FOR THESE SAME CORRECTIONS IN UNIT #2 & #3 |