Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T04CM03692

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2004 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
09/22/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LOOSE RUBBLE IN FOOTINGS 2) IMPROPER CLEARANCES AT FORMS TO BOTH CABLE AND REBAR 3) 1"MAXIMUM EXPOSED STRAND AT LIVE ENDS 4) MAKE SURE TENDON PROFILES ARE FLAT THROUGH SLAB (EXCEPT AT TURNDOWNS)
09/21/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :DENIED. 1) MOVE EARTH AWAY FROM FORMS 3' FOR PROPER TENDAN PROFILE @ STRESSING END. 2) MAINTAIN 3/4" CLEAR TO STRAND @ DEAD ENDS. 3) MAKE SURE SUB GRADE IS PROPER ELEVATION AND FLAT NECESSARY WHEN CHAIRS ARE ON GRADE AND TENDAN PROFILE IS FLAT.