Permit: T04CM03688

Parcel: 140383950

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
01/14/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/10/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 8D NAILS 6" ON CENTER SPACING ROOF SHEATHING INTO BIRD BOARD BLOCKS
2) REPLACE DAMAGED STUDS AT RSP4'S AND H2.5'S
3) STRAP CONDENSATE AND PLUMBING EXTERIOR
01/07/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS NOT CORRECTED
2) STOPPED INSPECTION
12/30/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
12/28/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE ALL DAMAGED CLIPS/TRUSS REPAIR NOT PER DETAIL
2) NAIL PROTECT CONDENSATE LINE FROM OUTSIDE
3) NAIL PROTECT ELECTRICAL FROM OUTSIDE AT PANEL
4) DBL TOP PLATE AT NORTH WALL NOT STAGGERED PER CODE
5) STOPPED INSPECTION
12/23/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FROM LAST INSPECTION: ALL SHEAR WALLS REQUIRE A TRANSFER CONNECTION SOME SHEAR WALLS ON THIS PLAN HAVE NOT BE LABELED FOR CROSS SECTION TO MATCH TRANSFER DETAILS ON DETAIL PAGE
3) 24" X 24" OSB GUSSET REPAIR TO TWO (DO1P) TRUSSES, ORIGINAL GUSSET, TO SMALL INSTALL 24" X 24" GUSSET
4) 3RD TRUSS STILL MISSING METAL GUSSET PLATE, MARKED ON FLOOR. ALL FOUR D01P TRUSSES ARE THE SAME EXCEPT, ONE SIDE HAS A SMALLER METAL GUSSET PLATE, SEE TRUSS DRAWINGS, TWO ARE INSTALLED BACKWARD
5) FRONT COLUMN P.A. STRAP NOT INSTALLED CORRECTLY INSTALL ALTERNATE
12/21/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) PLEASE WRITE OPTIONS ON PERMIT CARD EXAMPLE D01P TRUSSES AT PORCH OPTION
2) HAVE ENGINEER LABEL WHERE SHEAR TRANSFER DETAILS GO
3) NEED 24" X 24" GUSSETS ON TWO TRUSSES DO1P, BOTH SIDES PER DETAIL, INSTALLED BACKWARD, MISSING METAL GUSSET AT 3RD TRUSS NEXT TO EXHAUST FAN, DO1P TRUSS
4) P.A. STRAP AT FRONT COLUMN NEED A ALTERNATE EPOXY BOLT INSTALLED
12/20/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO LOT NUMBER POSTED
2) SILL PLATE NOT BEARING ON CONCRETE AT GARAGE TRIMMERS
3) LIST PLAN AND ELEVATION ON INSPECTION CARD. CANNOT TELL WHICH ELEVATION APPLIES. INSPECTED PER ELEVATION "A"
4) HOLDOWN AND AB AT ENTRY POST ? BEYOND USE
5) PROVIDE TRUSS REPAIR DOCUMENTS
12/16/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO TRUSS CALC'S ON SITE
2) FRONT POST HAS AN OVERSPALLED HOLDOWN
3) REAR POST HOLDOWN NOT NAILED
4) PROVIDE ENGINEERING AND CITY APPROVED OSB GUSSET REPAIR FOR TWO TRUSSES REAR OF HOUSE
5) STOPPED INSPECTION, HAVE SUPERVISOR AND TRADES WALK HOUSE BEFORE RECALL