Permit: T04CM03686

Parcel: 140383990


Addresses:

5851 E CHAUCERS DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/04/2005 FRAMING Approved IVRS - Inspection :*
02/03/2005 FRAMING Partial Approval IVRS - Inspection :*
1) SHIM ALL HEADERS
2) OK TO INSULATE
01/31/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
#5 SHEER IN MASTER BATH REMOVED
#7 INSP DATED 1-18
PROVIDE APPVD TRUSS REPAIRS BY COT
01/28/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO WATER TEST DWV
INSTALL NAIL PROTECTION ELECTRIC AND PLB THROUGHOUT
PLAN CALLS FOR 14" AND 18" COMBUSTION AIR GARAGE WALL TOP AND BOTTOM
STOPPED INSPECT RE FEE DUE
01/26/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY, CANCEL PER CONTRACTOR
01/24/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INCOMPLETE-ITEMS NOT CORRECTED
01/18/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WINDOW NORTH WEST NOT COMPLETE
2) FIREBLOCKS TO HIGH AT WATER HEATER PLATFORM
3) NO TEST ON DWV'S
4) FIREBLOCK BLOWN AT DRYER VENT AND WASHER
5) MID HEIGHT BLOCK MISSING AT FRONT BEDROOM
6) 8' FIREBLOCKING MISSING AT BEDROOM 3
7) PLUMBERS TAPE NOT ALLOWED FOR VENT SUPPORT
8) STOPPED INSPECTION
01/13/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WRONG TYPE OF GAUGE ON WATER LINES
2) GAS PRESSURE TEST GUAGE INOPERABLE
3) MOVE ELECTRIC WIRES AWAY FROM B-VENT
4) NO TEST ON DWV'S
5) STOPPED INSPECTION
01/03/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)LATH NOT COMPLETE