Permit: T04CM03683

Parcel: 106050730

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM03683

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)NOTICE INSIDE ELECTRIC SERVICE TO READ; "THIS BUILDING HAS NON-METALLIC WATER PIPING" 2)WHEN A DISHWASHER AIR BREAK FITTING IS OMITTED, THE DRAIN HOSE IS TO BE LOOPED TO WITHIN 2" OF DRAINBOARD HEIGHT 3)PLUMBING FINAL OK 4)OK FOR C/O PENDING ANY OTHER INSPECTION