Permit: T04CM03683

Parcel: 106050730

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T04CM03683

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection :* OK TO CLEAR CABLE DROP ONLY NO METER /NO TEMP SERVICE. CORRECTIONS REQUIRED 1) UNTWIST GROUNDING CONDUCTORS AND LAND EACH CONDUCTOR INTO SEPARATE TERMINALS. DO NOT GROUP GROUNDS INTO A SINGLE TERMINAL. 2. TRIM CABLE ENDS TO ELIMINATE "SHINER" ENDS. 3. SUPPORT GROUND WIRES BY CLAMPING TO WALL. 4) YOU MAY ELIMINATE THE GROUND BOND TO COLD WATER PIPE. 5) SEPARATE ( UNTWIST) ROMEX GROUNDS AND LAND INTO INDIVIDUAL TERMINAL SCREW CLAMP. 6) TRIM CIRCUIT WIRES TO ELIMINATE "SHINER" AT CIRCUIT BRAKERS. THANK YOU.
11/10/2004 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :* OK TO CLEAR