Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T04CM03683
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* OK TO CLEAR CABLE DROP ONLY NO METER /NO TEMP SERVICE. CORRECTIONS REQUIRED 1) UNTWIST GROUNDING CONDUCTORS AND LAND EACH CONDUCTOR INTO SEPARATE TERMINALS. DO NOT GROUP GROUNDS INTO A SINGLE TERMINAL. 2. TRIM CABLE ENDS TO ELIMINATE "SHINER" ENDS. 3. SUPPORT GROUND WIRES BY CLAMPING TO WALL. 4) YOU MAY ELIMINATE THE GROUND BOND TO COLD WATER PIPE. 5) SEPARATE ( UNTWIST) ROMEX GROUNDS AND LAND INTO INDIVIDUAL TERMINAL SCREW CLAMP. 6) TRIM CIRCUIT WIRES TO ELIMINATE "SHINER" AT CIRCUIT BRAKERS. THANK YOU. | |
11/10/2004 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK TO CLEAR |