Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :CHASTE NIPPLE NOT APPROVED FOR USE WITH LB USE PROPER HARDWARE TO ATTACH GROUND BAR TO BOX & CLEAN SURFACE UNDER LUGS ONE CONDUCTOR PER LUG |
|
| 08/23/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/NOT READY 1) PLANS NOT REFLECTIVE OF WORK INSTALLLED 2) SUPPORT M/C CABLE AS PER CODE. 3) TIGHTEN LOOSE FITTINGS 4) PLEASE PROVIDE AUTHURAZATION OF USE OF M/C CABLE . PLANS CALL FOR CONDUIT. 5) OLD VDV CABLES PER 90.4, TO BE AS PER 725.2, 800.2, 725.6 & 800.6 |