Permit: T04CM03665

Parcel: 136384460

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/13/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/11/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*1) PANEL SCHEDULE TO BE CORRECTED PLUS ONLY HAS ONE ARC FAULT BREAKER-SHOULD HAVE2. 2) NO POWER ON BATHROOM GFI -CB ON. 3) NO POWER ON WASHER RECEPTACLE -CB ON. 4) PANEL COVER PRESSING ON WIRING INSIDE IT FIT WIRING INTO PANEL SO WIRE NOT PRESSED IN. 5) DISCONNECT FOR AC CANNOT FOR HEAT STRIP LIFT FLEXS OFF ROOF.