Inspection History Details
Permit: T04CM03627
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/14/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) SAME AS LAST INSPECTION, NOTHING DONE |
|
| 01/13/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/11/2005 | FRAMING | Partial Approval | IVRS - Inspection :*/1)FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE - FRAME OK 2)3" C.O. MISSING @ MASTER TOILET 3)WATER LINES OK 4)OK TO INSULATE | |
| 01/07/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 2) NO TEST ON DWV'S 3) TUBS NOT GROUTED 4) MOVE WATER LINES AWAY FROM CAT WALK 5) W.C. RINGS NOT INSTALLED 6) 3" CLEANOUT MISSING AT MASTER BATH 7) LEAK AT MANIFOLD IN MASTER BATH |
|
| 01/04/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/30/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)SEAL AROUND T&P STUB OUT 2)EAST SIDE OF HOUSE NOT COMPLETE (LATH) 3)ROOF NOT DRIED IN 4)NO TEST ON DWV'S 5)NO TEST ON GAS LINE 6)NO W.C. FLANGES 7)MOVE FLEX DUCT AWAY FROM GUSSETT PLATER 8)PROVIDE A COMPLETE SET OF APPROVED PLANS. STOPPED INSP |