Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM03616
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL PROPER CONNECTION W/HTR ELECTRIC FLEX TO WALL NOT SECURE 2) LOOSE RECEPTACLE EAST FRONT BEDROOM, ALSO MIDDLE BEDROOM, LOOSE RECEPTS. THRU-OUT 3) HVAC ON ROOF, NEED A FACTORY LABEL NOT PAPER, CIRCUIT AMPACITY IS 56.1 #8 CU WIRE IS TO SMALL, DISCONNECT HAS NO FUSE RECEPT. YOU NEED 2 POLE 60/60 BREAKER 4) SCREWS STRIPPED IN ELECTRIC FALSE/COVER 5) CAULK THERMO STAT TO ROOF JACK 6) NO SEWER CARD IN FILE 7) DISCONNECT BOX ON ROOF IS LOOSE 8) NEED A VENT IN CONDENSATE LINE |
|
| 12/14/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS 2) LOWER NORTH CLEANOUT TO GRADE 3) PROVIDE ACCESS TO ATTIC 4) UNABLE TO TEST SMOKE ALARMS, REMOVE DUST COVERS 5) NO POWER TO PORCH GFI |
|
| 12/13/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS OR PERMIT ON SITE 2) NO ADDRESS POSTED |
|
| 12/10/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ADDRESS POSTED 2) ADD GFCI OUTLET IN MASTER BATH |