Permit: T04CM03614

Parcel: 12709012C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM03614

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*/ 1) ABOVE CEILING APPROVED 2) WILL NEED ACCURATE CITY APPROVED PLAN AS BUILT ON THE LAY IN FIXTURE TYPE, RE-CALC AND VOLTAGE CHANGE FROM 277 TO 120 VOLT
10/04/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :VDV CABLES LAYING ON GRID
SUPPORT WIRES TO BE ATTACHED BOTH ENDS
SUPPORT M/C CABLE & CONDUIT & FLEX AS PER CODES
FILL UNUSED OPENINGS IN BOX
FINISH INSTALLATION EXIT LIGHTS AS PER PLAN
PLEAS REVISE PLANS FOR 2X2 FIXTURES