Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM03590
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2004 | ELECTRIC - ABOVE CEILING | Approved | ||
11/05/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/05/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ 1) ALL EXCEPT 101, 102, 100, 136, 135 AND 134 | |
11/03/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/1)FINISH SUPPORTING VDV CABLES - NOT TO USE CEILING GRID WIRES, MUST BE INDEPENDANT WIRES 2)CLOSE UP ABANDONED BOXES 3)SUPPORT FLEX CONDUITS AS PER CODE, AND M/C CABLE | |
11/01/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) ABANDON CABLES VDV TO BE AS PER 725.2 AND 800.2 2) OK ROOMS 118-128, 104, 143 AND 142 | |
10/15/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ |