Permit: T04CM03588

Parcel: 141016170

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03588

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2005 FRAMING Approved IVRS - Inspection :*
01/14/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) REMOVE SCREW IN KITCHEN VERT. DRAIN PIPE
2) NEED STRICKER OUTLET FOR GAS RANGE
3) NEED TO CALC. LOAD ON HGLS6-25 BEAM HANGER, 16D SINKERS USED INSTEAD OF 16D COMMONS
4) DRYER DUCT USE RIDGID DUCT NOT FLEXIBLE
5) MISSING VERTICAL BACKING FRONT TOILET COMPARTMENT
6) NEED DWV H20 TESTED
7) SW3 1ST FLOOR, LOOSE NUT, MISSING HTT26 AND A.B. AT 16" ON CENTER 1/2 DIAMETER
8) ? CUT CEILING OF MASTER CLOSET
9) NEED OUTLET 6' FROM CORNER BEDROOM NORTHWEST
10) TOP OF STAIRS NEED SUPPORT BELOW FOR EACH SIDE OF HEADER BEAM CIRCLED ON FLOOR
11/16/2004 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) CANNOT INSPECT INTERMEDIATES UNTIL HOUSE LATHED
2) SHEAR WALLS NOT NAILED BELOW LEDGERS-SEE 5/D-1
3) NO LADDER-ROOF NOT INSPECTED