Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM03588
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2005 | FRAMING | Approved | IVRS - Inspection :* | |
01/14/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) REMOVE SCREW IN KITCHEN VERT. DRAIN PIPE 2) NEED STRICKER OUTLET FOR GAS RANGE 3) NEED TO CALC. LOAD ON HGLS6-25 BEAM HANGER, 16D SINKERS USED INSTEAD OF 16D COMMONS 4) DRYER DUCT USE RIDGID DUCT NOT FLEXIBLE 5) MISSING VERTICAL BACKING FRONT TOILET COMPARTMENT 6) NEED DWV H20 TESTED 7) SW3 1ST FLOOR, LOOSE NUT, MISSING HTT26 AND A.B. AT 16" ON CENTER 1/2 DIAMETER 8) ? CUT CEILING OF MASTER CLOSET 9) NEED OUTLET 6' FROM CORNER BEDROOM NORTHWEST 10) TOP OF STAIRS NEED SUPPORT BELOW FOR EACH SIDE OF HEADER BEAM CIRCLED ON FLOOR |
|
11/16/2004 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) CANNOT INSPECT INTERMEDIATES UNTIL HOUSE LATHED 2) SHEAR WALLS NOT NAILED BELOW LEDGERS-SEE 5/D-1 3) NO LADDER-ROOF NOT INSPECTED |