Permit: T04CM03587

Parcel: 141016180

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T04CM03587

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/16/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CANNOT INSPECT INTERMEDIATES UNTIL HOUSE LATHED
2) SEVERAL HOLDOWNS WRONG LOCATION, INSTALL ALTERNATE
3) OSB SHEAR NOT NAILED AT 8 FT SEAM
11/01/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) OK TO COVER LEDGERS 2) EAST WALL NORTH CORNER SOUTH HOLDOWN NOT ON SHEARWALL-REPLACE 2) EAST WALL SOUTH SHEAR WALL HOLDOWNS NOT IN SHEAR WALL-REPLACE 3) PLAN CALLS FOR SIMPSON ? JOIST HANGERS . U.S.P. THOZ1040 USED. HAVE PLAN REVISED TO AS BUILT NAILS CANNOT BE DRIVEN INTO LAMINATE OF TJI. PROVIDE PRODUCT INSTALLATION MANUAL