Permit: T04CM03580

Parcel: 133231410


Addresses:

7701 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/08/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
2) LEE RAY, PLEASE PICK UP A COPY OF THE 3RD PARTY TEST REPORT ON FIRE/SMOKE DAMPERS
09/07/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKES IF WITHIN 10'
2) PROVIDE A CONDENSATE DRAIN ON 1 UNIT
3) VENTS MUST BE DOWNSTREAM OF THE TRAP
4) PLEASE PROVIDE THE TEST REPORT FOR THE FIRE DAMPERS AND SMOKE DETECTORS AS SPECIFIED ON PLANS M-1 NOTE 18