Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM03580
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/08/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/02/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT WIRE NEEDED FOR EXIT LIGHT BOXES 2) NO WORK PROGRESS FOR VDV CABELING |
|
08/30/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PLEASE COMPLETE #2 AND 6 OF PREVIOUS INSPECTION 2) PLEASE LEAVE TILE OPEN TO INSPECT SIGN TRANSFORMERS 3) INSTALL EXIT LIGHTING |
|
08/26/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOW ARE 2 X 2 SECURED TO GRID ? 2) VDV TO BE SUPPORTED AT 6' INTERVALS AND INDENPENDENTLY AS PER 300.11 3) FILL UNUSED OPENINGS IN BOXES 4) SUPPORT CONDUIT WITHIN 3' OF BOXES 5) CONDUIT CROSS IN BOX COVER PREVENTING ACCESS 6) HAVE BLDG INSPECTOR VERIFY FIRE WALL ASSEMBLY PENITRATIONS |
|
08/23/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FIXTURES TO HAVE 2 SUPPORT WIRES FROM OPPOSITE CORNERS 2) WIRE TO BE INDEPENDENTLY SUPPORTED 300.11 |