Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2005 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/26/2005 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IBC SECTION 719 LIMITS FLAME SPREAD OF INSULATION TO 25 AND SMOKE SPREAD TO 450. THE FACING OF YOUR INSULATION DOES NOT MEET THIS REQUIREMENT 2) OK TO PLACE ? TILE, IF YOU LEAVE LADDER SO I CAN SEE INSULATION FIXED |
|
| 08/23/2005 | BUILDING ABOVE CEILING | Not ready for Inspection | 1) SEAL ALL PENETRATIONS AND DUCT AT FIRE WALLS |