Permit: T04CM03576

Parcel: 129080180


Addresses:

1747 E 23RD ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/16/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :* 1) CORRECTIONS MADE OK. 2) OK TO COVER NOTE: CONTRACTOR TO REMOVE ALL FOREIGN MATER, ROCK, & DEBRIS BEFORE BACKFILLING
03/15/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999* AIR OR WATER TEST SHALL BE ON SYSTEM AT TIME OF INSPECTION.
03/14/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SOIL WATER TEST IS OK. 2) DWV SYSTEM UNDERGROUND IS OK. 3) NOTE: CANNOT BUNDLE HOT & COLD WATER DUE TO TRANSFER OF HEAT AND THERE IS A BIG KINK ON THE 1 1/4" U.G COLD LOOP. 4) YARD WATER LINE FROM METER TO BLDG. SERVICE IS OK. NOTE: SHALL SEE CONNECTION TO BACKFLOW PREVENTER.
03/13/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE A 3" VENT @ WATER CLOSET. 2) RE TEST SYSTEM. 3) HCS CONNECTION IS OK 4" BLDG. SEWER OK TO BACKFILL ONLY. 4) YARD WATER LINE NO READY.