Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM03566
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/01/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) JUNCTION BOX TO BE GROUNDED 250.148 2) PLEASE PROVIDE PHYSICAL PROTECTION FOR PVC CONDUITS 3) IDENTIFY GROUNDING CONDUCTORS 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE. NEED AN APPROVED EXTENDER RUN 314.20/370-20 |