Permit: T04CM03566

Parcel: 11307088B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM03566

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/03/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*APPROVED
02/02/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250* 1) RECESSED FIXTURES NOT PROPERLY TETHERED TO SEISMIC WIRE. 2) OPEN " J" BOXES. 3) IMPROPERLY " CLIPPED" FLUORESCENT DROP IN FIXTURES. SCREW TO CEILING GRID. 4) DO NOT SUPPORT ANY ELECTRICAL CABLES, CONDUIT, ETC. FROM CEILING GRID SUPPORT WIRES. INSTALL SEPARATED WIRES. THESE MUST BE TIED TO THE CEILING GRID T-BAR.