Permit: T04CM03565

Parcel: 117141070


Addresses:

58 W CUSHING ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM03565

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK C OF O
11/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NEW CONDUIT ENTERING PANEL TO HAVE A SEALING LOCK NUT TO PREVENT WATER GETTING IN ABOVE BUSS
2) CIRCUIT BREAKER FILLER PLATE MISSING
3) CONDUIT COMING INTO PANEL REQUIRES SUPPORT PER CODE WITH IN 3' OF PANEL
4) GROUND WIRE AT BOTTOM OF PANEL OUTSIDE HAS BEEN CUT
5) WATER HEATER REQUIRES A DISCONNECT MEANS, SEE PLANS
6) OK FOR TEMP C OF O