Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK C OF O | |
| 11/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEW CONDUIT ENTERING PANEL TO HAVE A SEALING LOCK NUT TO PREVENT WATER GETTING IN ABOVE BUSS 2) CIRCUIT BREAKER FILLER PLATE MISSING 3) CONDUIT COMING INTO PANEL REQUIRES SUPPORT PER CODE WITH IN 3' OF PANEL 4) GROUND WIRE AT BOTTOM OF PANEL OUTSIDE HAS BEEN CUT 5) WATER HEATER REQUIRES A DISCONNECT MEANS, SEE PLANS 6) OK FOR TEMP C OF O |
|
| 11/08/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |