Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/27/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :*/ 1) OK WALLS/HARD LIDS |
| 09/21/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection : NOTES: 1) WIRING METHODS IN PATIENT CARE AREAS MUST COMPLY WITH NEC 517-13 ROMEX NOT APPROVED. SEE NOTE ON SHEET E-1 TOP OF PAGE. 2) THERE MUST BE 1 1/4" MIN DISTANCE BETWEEN CABLE AND FINISHED WALL, USE SUPPORTS TO HOLD CABLE BACK TO ACCOMPLISH THIS PLEASE. |