Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM03565
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) OK WALLS/HARD LIDS | |
09/21/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : NOTES: 1) WIRING METHODS IN PATIENT CARE AREAS MUST COMPLY WITH NEC 517-13 ROMEX NOT APPROVED. SEE NOTE ON SHEET E-1 TOP OF PAGE. 2) THERE MUST BE 1 1/4" MIN DISTANCE BETWEEN CABLE AND FINISHED WALL, USE SUPPORTS TO HOLD CABLE BACK TO ACCOMPLISH THIS PLEASE. |