Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04CM03565

Parcel: 117141070


Addresses:

58 W CUSHING ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/27/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) OK WALLS/HARD LIDS
09/21/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection : NOTES: 1) WIRING METHODS IN PATIENT CARE AREAS MUST COMPLY WITH NEC 517-13 ROMEX NOT APPROVED. SEE NOTE ON SHEET E-1 TOP OF PAGE. 2) THERE MUST BE 1 1/4" MIN DISTANCE BETWEEN CABLE AND FINISHED WALL, USE SUPPORTS TO HOLD CABLE BACK TO ACCOMPLISH THIS PLEASE.