Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/23/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/19/2005 | BUILDING - FINAL | Cancelled | IVRS - RI canceled | |
| 08/17/2005 | BUILDING - FINAL | Denied | AFTER HOURS INSPECTION PER S. LONG 1) 36" X 36" STOOP NEEDED WEST EXIT DOOR 2) COMMON BATH GFCI DOES NOT TEST 3) SPLICED WIRES MECHANICAL ROOM SUB PANEL MUST TERMINATE IN APPROVED BOX 4) EXPOSED ROMEX IN OLD BATHROOM 5) OLD CIRCUITS TEST OPEN GROUND 6) NO POWER BEDROOM 2 7) NO POWER LIVING CIRCUITS 8) PAINT ROOF VENTS |
|
| 08/17/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI IN BATH NO POWER 2) WATER HEATER B-VENT NOT INSTALLED 3) SMOKE DETECTORS MUST BE 36" FROM REGISTERS 4) NO POWER TO SOME OUTLETS AND SOME HAVE OPEN GROUNDS 5) PROVIDE 36" X 36" STOOP AT SIDE DOOR 6) GFCI IN BATH SELF TRIPS 7) NO POWER TO OUTLET IN HALLWAY 8) OPEN GROUND AT OUTLET DINING 9) PROVIDE PROOF OF INTERMEDIATE INSPECTIONS |