Permit: T04CM03527

Parcel: 115154590

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/15/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/31/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#1 - PAINT ALL PVC CONDENSATE PIPING ON ROOF
#1 & #2 - HEAT STRIPS NOT INDICATED ON ROOFTOP UNITS
#1 & #2 - PROVIDE FILTERS IN R/A GRILL
09/11/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GATES LOCKED
DO NOT SCHEDULE INSPECTIONS
IF THE SITE WON'T BE OPEN!
07/26/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS
- PAINT EXPOSED PVC W/LATEX PAINT
- ELEC. DISCONNECT NOT SUPPORTED PROPERLY
- INCORRECT WIRING METHODS ON ROOFTOP
- PROVIDE SERVICE RECEPTACLE
- PERMANENTLY I.D DATA PLATE WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY