Permit: T04CM03527

Parcel: 115154590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECEPTACLE IN MASTER BEDROOM UNIT #2 SHOWING REVERSE POLARITY
2) GFI RECEPTACLE ON ROOF TO UNIT #2 NOT RESETING
11/15/2007 ELECTRIC - FINAL Not ready for Inspection WORK IN PROGRESS
10/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ROMEX NOT ALLOWED AS A CORD
2. USE APPROVED PLATES FOR WATER HEATER MAKE UP BOX
3. PROVIDE DISCONNECTING MEANS FOR WATER HEATER
4. PANEL SCHEDULE TO BE LEGIBLE
5. BOXES MORE THAN 1/4" 314.20
6. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
7. FILL IN EXCESS GAP AROUND PANEL - 408.2 & 314.21
8. NO FURTHER INSPECTIONS UNTIL VERIFY QUALIFIED ELECTRICAL PERSON
09/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. PROPERLY IDENTIFY COMPRESSOR DATA PLATES AS TO HEAT STRIPS (IF ANY) ARE INSTALLED - NEC 424.29, 440.4
2. CONDENSATE DRAIN LINE NOT TO BE IN FRONT OF DISCONNECT -- NEC 110.26
3. DINING ROOM 3 WAY LIGHT SWITCH NOT WIRED PROPERLY NOT WORKING
4. INSTALL RANGE ANTI-TIP BRACKET
5. RANGE RECEPTACLE AND CORD TO BE 4 WIRE
INSTALL RECEPTACLE COVER, CONNECTOR FOR CORD AND REMOVE RANGE BONDING JUMPER
6. PROVIDE CONNECTOR FOR HOOD CORD
7. SMOKE DETECTORS NOT INTER-CONNECTED
8. BATH GFI NOT TESTING/WIRE WRONG?
9. PROVIDE ARC FAULT PROTECTION FOR ALL BEDROOMS RECEPTACLES, LIGHTS AND SMOKE DETECTORS
10. PANEL DIRECTORY NOT PROPERLY IDENTIFIED
11. USE ONLY SQUARE D HOMELINE BREAKER IN PANEL
12. PANEL NOT GROUNDED - NEUTRAL AND GROUNDS TO BE SEPARATED IN SUB-PANEL
13. INSTALL ALL LIGHT BULBS
14. WATER HEATER TO BE GROUNDED AND HAVE PROPER WIRING METHOD (RACEWAY AND PROPER FITTINGS)

WORK TO BE DONE BY QUALIFIED ELECTRICIAN INSPECTION FOR #1 ONLY -- GO THROUGH UNITS
07/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR FINAL WHEN #1 METER IS IN

NOTE: USE ONLY SQUARE D BREAKERS IN SUB-PANEL