Permit: T04CM03527

Parcel: 115154590

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/11/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED PER CONTRACTOR
06/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER ELECTRICAL
2) REMOVE BONDING JUMPER IN SUB-PANELS FROM NEUTRAL AND PUT IT ON GROUNDS
04/20/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FEEDERS FOR SUB-PANELS NEED TO BE IN RACEWAY OR PART OF A CABLE WITH OUTER JACKET - NOT OPEN WIRING.
2. GROUNDS AND NEUTRALS TO BE SEPARATED IN SUB-PANELS.
3. KITCHEN COUNTER CKT'S SHOULD ONLY SERVE LOADS ALLOWED AND NO OTHERS.
4. INSTALL RANGE CKT.