Permit: T04CM03527

Parcel: 115154590

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
02/10/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*A
01/19/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED VERIFICATION OF ALL PROPERTY LINES
2) SETBACKS TO WEST CALL FOR 10' (8'-4" EXISTS TO CHAIN LINK FENCE)
3) WIDTH OF HOUSE NOT PER PLAN
4) REBAR TO OVERLAP 30 BAR DIAMETERS
5) REBAR TO HAVE 3" CLEARANCE REBAR TO DIRT
6) UFER CLAMPS TO HAVE ALL BRASS SCREWS
7) STOPPED INSPECTION