Permit: T04CM03507

Parcel: 107123780


Addresses:

280 W MCFAR DR

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
04/28/2005 ROOF NAILING Approved
10/14/2004 ROOF NAILING Partial Approval IVRS - Inspection :*
10/08/2004 ROOF NAILING Denied IVRS - Inspection :
1) CANNOT APPROVE ROOF OR CLIP UNTIL MASONRY WALLS ARE INSPECTED AND APPROVED BY CITY OF TUCSON. 2) 2 X 6 PORCH BEAM TOO SHORT. NOT BEARING ON ?? TO GROUND. 3) NO CITY APPROVED TRUSS DRAWING ON SITE. 4) EACH 3PT TRUSSES INSTALLED BACKWARD. PROVIDE ENGINEERS APPROVED REPAIR. 5) TRUSS O.SB SHEATHING MISSING. 6) TRUSS BRACES A MISSING TRUSSES B1, B6, B7. OK TO INSTALL VAPOR BARRIER ON GABLE ROOF DO NOT LOAD ROOF WITH STEEL PANELS. STOPPED INSP TOO MANY ITEMS.
10/06/2004 ROOF NAILING Not ready for Inspection IVRS - Inspection :*