Inspection History Details
Inspection Status: Denied
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/15/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/14/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS 2) HOUSE BEING PAINTED INSIDE |
|
| 01/18/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE INSPECTION DATED 1/12/05-NOTHING DONE |
|
| 01/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER LINE DRILLED THROUGH TOP CHORD OF FLOOR TRUSS AND CUT, PROVIDE APPROVED ENGINEERING AND CITY OF TUCSON 2) SEAL BOTTOM OF TUB INTO 2ND FLOOR 3) PROVIDE CITY OF TUCSON APPROVED REPAIR FOR KITCHEN WALL |
|
| 01/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)DWV'S HAVE TO BE DRY FOR INSPECTION, PLUMBER JUST FILLED SYSTEM 2)SEAL PENETRATIONS UNDER NB 3)SEAL MECHANICAL CHASE INTO ATTIC 4)PROVIDE APPROVED REPAIR FOR KITCHEN WALL APPROVED BY CITY OF TUCSON 5)RE-NAIL BRACES @ NORTH EAST 2ND FLOOR |
|
| 01/05/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DWV'S LEAKING 2) MAIN WATER LINE VERTICAL RUN DOES NOT HAVE THE 1 1/2 CLEARANCE FROM EDGE OF STUD 3) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE 4) NAIL PROTECT PLUMBING 5) MOVE ELECTRIC WIRE 6) SECURE WATER LINE AT POWDER ROOM 7) STOPPED INSPECTION |