Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) PLBG. FINAL IS OK OK FOR C OF O | |
| 04/21/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAN NOT CANT THE P-TRAP ON INDERECT WASTE 2) SHALL PROVIDE PROPER TRANSITION COUPLING FROM ABS TO CAST IRON @ FLOOR SINK VENT. 3) SHALL PROVIDE PRIMER ON ALL PVC FITTINGS PRIOR TO APPLYING PVC GLUE. |
|
| 04/20/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A TESTALE BACKFLOW PREVENTER@ EACH DISPENSER UNIT. TESTED AND CERTIFIED PRIOR TO FINAL. 2) SHALL PROVIDE CAST IRON VENT ALL THE WAY TO SLAB. 3) SHALL PROVIDE TYPE M COPPER FOR WATER DISTRIBUTION. |
|
| 04/19/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/20/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |