Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/14/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SEPERATE CIRCUIT FOR HEAT STRIP PER PLAN 2) PLAN CALLS FOR 20 AMP CIRCUIT #14 WIRE USED (SHOULD BE #12) 3) HAVE PLAN CHANGED REGARDING CHANGE OF PONY WALL AT TOP OF STAIRS TO WRONG AT IRON RAIL AND DELETE 4) ELECTRIC OUTLET IF ALLOWABLE 5) STOPPED INSPECTION |