Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/01/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCREEN MISSING AT WASHER PAN DRAIN 2) AT SRV, ROMEX NEEDS TO BE SECURED WITHIN 8" FROM BOX 3) PROVIDE COVER PLATE FOR ELECTRIC JUNCTION BOX AT CLOSET UNDER STAIRS 4) PROVIDE ALL SPECIAL CERTS |
|
| 02/28/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC BOXES AT REAR EXPOSED TO WEATHER 2) SCREEN MISSING AT WASHER DRAIN 3) OUTLET IN GARAGE NOT GFCI PROTECTED 4) ROMEX MUST BE SECURED WITHIN 8" FROM BOX AT SRV 5) WASHER DRAIN PAN NOT INSTALLED 6) LIGHT IN CLOSET UNDER STAIRS TO CLOSE TO COMBUSTIBLES |
|
| 02/25/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER VENT NOT CONNECTED 2) ALL GARAGE ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) DISH WASHER DRAIN MUST LOOP TO WITHIN 2" OF FLOOD RIM OR INSTALL AIR GAP DEVICE 4) HAND RAIL ON WINDOW STAIRS MUST BE CONTINOUS 5) NO LADDER ACCESS TO ATTIC FURNACE 6) STOPPED INSPECTION |
|
| 02/24/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |