Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/07/2005 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection No plan or permit on site |
|
| 02/03/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED ON SITE BY JAMES (K.B. HOMES) |
|
| 02/02/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE LAST INSPECTION DATED 1/28/05 2) PROVIDE 6" CLEARANCE FOR WATER LINES FROM B-VENT 3) REMOVE DRYWALL FOR INSPECTION |
|
| 01/28/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 FIRE BLOCK MISSING AT WATER HEATER STAND 2 BLOCK HIGH AND LOW C+R 3 BLOCK RETURN AT 2ND FLOOR LANDING 4 FIRE BLCOK MECH CHASE 5 BLOWN FIRE BLOCK AT BLR ABOVE GARAGE 6 STAP NORTH EAST WALL MISSING NAILS 7 WH VENT CHASE NOT FIRE BLOCKED 8 PROVIDE SMOKE DETECTOR OUTSIDE BEDROOMS 9 PROVIDE 1" CLEARANCE FROM COMBUSTIBLES 10 NEED CLARIFICATION ON DETAIL 2SD2 |
|
| 01/26/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED ON SITE BY JAMES (K.B. HOMES) |
|
| 01/24/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED ON SITE BY JAMES (K.B. HOMES) |