Permit: T04CM03473

Parcel: 125041620


Addresses:

2310 E 1ST ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/04/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
02/01/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEWER LINE MUST BE 12" BELOW GRADE OR USE METAL PIPE
2) WEST SIDE OF ADDITION IS 2 FEET FROM PROPERTY LINE NO OPENINGS ALLOWED WITHIN 3 FEET OF PROPERTY LINE
3) PROVIDE CITY APPROVED DETAIL FOR FIRE RATING COMBUSTIBLE MATERIAL WITHIN 3 FEET OF PROPERTY LINE
4) HOLDOWNS MUST BE ATTACHED TO FULL LENGTH DBL STUDS AND ALL HOLES FILLED WITH NAILS
5) PLAN CALLS FOR 3 1/8" X 9" GLB AT RIDGE. DBL 2 X 12 USED. BUILD TO PLAN OR REVISE PLAN TO AS BUILT
6) GLB REQUIRES 4 X 4 POSTS NOT INSTALLED
7) W/C AND SHOWER NOT PROPERLY VENTED
8) NAIL PROTECT ALL PLUMBING WITHIN 1 1/4" OF FRAME SURFACE
9) ROOF NAIL OK BUT GLB SUPPORT NOT PER PLAN