Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2004 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection :* | |
| 12/27/2004 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME 2) NO PLANS ON SITE |
|
| 12/21/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection :* 1) 1ST 4' LIFT 2) REVISION D-1 OPTION 8" CMU |
|
| 12/16/2004 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REINFORCING STEEL MUST BE INSTALLED AND EXTEND A MINIMUM OF 20" ABOVE INSTALLED BLOCK 2) A-2.1 SHOWS HEIGHT OF WALL TO BE 8'-11" CMU WITH FURR OUT BUT 2/A4 SHOWS WEST WALL TO BE WOOD FRAME. IF WOOD FRAME WHAT IS THE HEIGHT OF MASONRY WALL |
|
| 12/14/2004 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERTICAL REINFORCING STEEL MUST BE INSTALLED AND EXTEND A MINIMUM OF 20" ABOVE BLOCK. SEE 3/D1 |