Permit: T04CM03453

Parcel: 141012050


Addresses:

5337 S CIVANO BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM03453

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/09/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/3050-NOT REQUIRED. NO GAS TO BUILDING
12/06/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)READ ALL NOTES FROM 12/3/04 INSPECTION ON BOTH HOUSE & LOFT AND MAKE CORRECTION. NOTES PORTAIN TO BOTH UNITS
12/03/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) TEST ALL WASTE AND VENT PIPING WITH AIR OR WATER THRU ROOF
2) SUPPORT SECURE WASTE AND VENT PIPING EVERY 4' ON HORIZONTAL
3) PROVIDE MINIMUM 1/4" PER FOOT FALL ON WASTE PIPING
4) 30 PSI AIR TEST FROM METER TO STOVE AND DRYER (ONLY) OK
5) SECURE GAS PIPING AT DRYER LOCATION